Step | Action | Value | Yes | No | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | Were you sent here from the A/C System Performance Test? | -- | ||||||||||||||
2 |
Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section. Feel the liquid line before the expansion device. Is the liquid line cold before the expansion device? | -- | ||||||||||||||
3 | Feel along the surfaces of the following high side components for a sudden drop in temperature (the high side components should feel warm/hot from the compressor all the way to the expansion device).
Is there an abrupt drop in temperature noted along the surfaces of any of the listed components? | -- | ||||||||||||||
4 |
Is the liquid line extremely cold at the expansion device location and warm after the expansion device location? | -- | ||||||||||||||
5 | Feel along the surfaces of the following low side components for a sudden change in temperature.
Is there an abrupt temperature change felt along the surfaces of any of the listed components? | -- | ||||||||||||||
6 | Feel along the surfaces of low and high side components to compare the overall temperatures.
Are the overall temperatures of the low and high side components close to the same (both only mildly warm)? | -- | ||||||||||||||
7 |
Is the repair complete? | -- | -- | |||||||||||||
8 |
Is the weight of the recovered refrigerant charge equal to or above the specified value? | 0.57 kg (1.26 lb) | ||||||||||||||
9 | Recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Is the cooling performance improved? | -- | ||||||||||||||
10 |
Is the repair complete? | -- | -- | |||||||||||||
11 |
Are there metal flakes present? | -- | ||||||||||||||
12 |
Is there a large amount of debris collected in the shop towel? | -- | ||||||||||||||
13 | If the expansion device was restricted with a brown/black residue, perform the following:
Are the repairs complete? | -- | -- | |||||||||||||
14 |
Is there debris present in the compressor suction port? | -- | ||||||||||||||
15 |
Is there evidence of damage or debris? | -- | ||||||||||||||
16 |
If the expansion device does not show any signs of damage or debris:
Is there a large amount of debris collected in the shop towel? | -- | ||||||||||||||
17 |
Are there metal flakes present? | -- | ||||||||||||||
18 | If there was a large amount of debris collected in the shop towel from the compressor hose assembly:
Is the repair complete? | -- | -- | |||||||||||||
19 | Install the compressor hose assembly. Refer to Compressor Hose Assembly Replacement . Are the repairs complete? | -- | -- | |||||||||||||
20 |
Are the repairs complete? | -- | -- | |||||||||||||
21 |
Are the readings within the specified ranges? | -- | ||||||||||||||
22 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Symptoms - HVAC Systems - Manual or |