Table 1: | A/C System Reference Table |
Step | Action | Yes | No | ||||||
---|---|---|---|---|---|---|---|---|---|
DEFINITION: The V5 compressor is a variable displacement compressor which matches air conditioning demand by changing the stroke rather than cycling the clutch. A control valve is located in the rear head of the compressor. The control valve senses the compressor low side pressure and causes the compressor mechanism to change stroke. During extended periods of shutdown, liquid refrigerant collects in the compressor crankcase. This is normal. The cooling action may be delayed for up to 2 minutes until the refrigerant is pumped from the compressor crankcase. Because the V5 compressor always runs and the system does not cycle, these diagnostic procedures differ from those used for fixed displacement systems. Use these procedures in order to avoid needlessly replacing A/C components. Certain conditions which are normal to proper air conditioning system operation may lead an owner to wrongly suspect a problem. The air discharged from the air conditioning system may not feel as cold as expected under conditions of high humidity. The reason is that the vaporized moisture in humid air heats more effectively than dry air does, making the humid air harder to cool. In terms of overall comfort, however, the dryer dehumidified air coming from the air conditioning system during hot, humid weather evaporates more moisture on a person's skin, providing more of a cooling effect than might be felt from cooler but more humid air. This fact should be explained to an owner if no mechanical cause is found for a persistent complaint of insufficient cooling. | |||||||||
1 | Did you perform the A/C System Performance Test? | Go to Step 2 | |||||||
2 |
Did you find and correct the condition? | Go to Step 3 | |||||||
3 |
Is the repair complete? | Go to Step 4 | |||||||
4 | Inspect the blower motor for proper operation. Refer to Symptoms - HVAC Systems - Manual . Is the repair complete? | Go to Step 5 | |||||||
5 | Inspect the cooling fan system for proper operation. Refer to Symptoms - Engine Cooling in Engine Cooling. Is the repair complete? | Go to Step 6 | |||||||
6 |
Is the repair complete? | Go to Step 7 | |||||||
7 | Inspect for a slipping, damaged or missing compressor drive belt. Refer to Drive Belt Replacement in Engine Mechanical. Is the repair complete? | Go to Step 8 | |||||||
8 |
Are both pressures 345 kPa (50 psi) or higher? | Go to Step 10 | Go to Step 9 | ||||||
9 |
Is the repair complete? | -- | |||||||
10 |
Does the compressor clutch engage? | Go to Step 11 | |||||||
11 | Inspect the system for the following conditions:
Is there noise from the compressor? | Go to Step 12 | Go to Step 13 | ||||||
12 | Repair or replace the compressor. Refer to the following: Is the repair complete? | -- | |||||||
13 |
Important: This test is designed for typical garage conditions: 21-32°C (70-90°F) and no sun load. Normal discharge air temperature is typically at least 7°C (20°F) cooler than ambient temperature. This test is designed to create enough cooling load to cause the V5 to operate at full stroke. This procedure must be followed exactly for accurate test results.
Is there a noticeable temperature difference? | Go to Step 15 | Go to Step 14 | ||||||
14 |
Is the repair complete? | -- | |||||||
15 |
Important: Humidity and temperature variables can create borderline diagnostic conditions and increase the pressure range of a normally operating system. If possible, test a known good system in order to determine if the pressures are normal for the climatic conditions encountered. Do the pressures intersect in the grey side of the table? | Go to Step 16 | Go to Step 19 | ||||||
16 |
Does the line feel cold? | Go to Step 18 | Go to Step 17 | ||||||
17 | The refrigerant system is overcharged or there is air in the system. Evacuate and recharge. Refer to Refrigerant Recovery and Recharging and Leak Testing . Is the repair complete? | -- | |||||||
18 |
Is the repair complete? | -- | |||||||
19 | Do the pressures intersect in the striped side of the table? | Go to Step 20 | Go to Step 28 | ||||||
20 | Are the compressor High and Low side pressures within 207 kPa (30 psi) of each other? | Go to Step 21 | Go to Step 23 | ||||||
21 |
Are the compressor High and Low side pressures within 207 kPa (30 psi) of each other? | Go to Step 22 | Go to Step 13 | ||||||
22 |
Does the compressor clutch driver turn freely by hand? | Go to Step 26 | |||||||
23 | Is the Low side pressure 172-241 kPa (25-35 psi)? | Go to Step 24 | Go to Step 26 | ||||||
24 | The refrigerant is undercharged. Add 0.40 kg (14 oz) of refrigerant. Does the cooling performance improve? | Go to Step 9 | Go to Step 25 | ||||||
25 |
Is the repair complete? | -- | |||||||
26 |
Important: This control valve test is designed to create a low cooling load which causes the V5 to operate at less than full stroke. This procedure must be followed exactly for accurate test results.
Is the Low side pressure 172-241 kPa (25-35 psi)? | Go to Step 13 | Go to Step 27 | ||||||
27 | Replace the control valve. Refer to the following: Is the repair complete? | -- | |||||||
28 | The pressures intersect in the white or normal side of the table. The refrigeration system components are functioning properly. Inspect for restrictions or leakage within the heater case. Refer to Air Recirculation Malfunction in HVAC Systems - Manual. Is the repair complete? | -- |
Symptom | Possible Causes | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
High Side Pressure Above Specifications |
| ||||||||||||||||||
High Side Pressure Below Specifications |
| ||||||||||||||||||
Low Side Pressure Above Specifications |
| ||||||||||||||||||
Low Side Pressure Below Specifications |
| ||||||||||||||||||
Center Air Outlet Temperature Above Specifications |
| ||||||||||||||||||
Center Air Outlet Temperature Below Specifications | There is a blower malfunction causing insufficient air volume. Refer to Blower Motor Inoperative or Blower Motor Malfunction . |